{"id":252719,"date":"2024-10-19T16:41:15","date_gmt":"2024-10-19T16:41:15","guid":{"rendered":"https:\/\/pdfstandards.shop\/product\/uncategorized\/bsi-pd-iec-ts-62735-22016\/"},"modified":"2024-10-25T12:01:18","modified_gmt":"2024-10-25T12:01:18","slug":"bsi-pd-iec-ts-62735-22016","status":"publish","type":"product","link":"https:\/\/pdfstandards.shop\/product\/publishers\/bsi\/bsi-pd-iec-ts-62735-22016\/","title":{"rendered":"BSI PD IEC\/TS 62735-2:2016"},"content":{"rendered":"

This clause of Part 1 is applicable except as follows:<\/p>\n

Replacement:<\/i><\/p>\n

Replace the first paragraph with the following:<\/i><\/p>\n

This part of IEC 62735, which is a technical specification, applies to plugs and fixed socketoutlets for class I equipment with two active contacts plus an earthing contact, a rated power of 5,2 kW and a rated voltage range from 294 V to 400 V d.c. They are intended to power d.c. information and communication technology equipment only.<\/p>\n

The 2,6 kW system complying with Part 1 is safely compatible with the system complying with this part as it is possible to insert the 2,6 kW plug in the 5,2 kW socket-outlet but it is not possible to insert the 5,2 kW plug into the 2,6 kW socket-outlet.<\/p>\n

Replace the third paragraph with the following:<\/i><\/p>\n

The maximum current for the plug and the socket-outlet is<\/p>\n